Overcurrent devices in the SEPSS are coordinated for selective tripping on short circuit, with available fault current from both utility and emergency source checked; ratings of integral fuses and breakers are coordinated with downstream devices so the least critical part of the load is cleared first; where the ECE limits current electronically, internal transfer switches move the load to the alternate source; and EPSS overcurrent devices are reachable only by authorized persons.