AS/NZS 4836:2023 Safe Working on or near Low-Voltage and Extra-Low Voltage Electrical Installations and Equipment
Section 4: Risk control for specific situations – AS/NZS 4836:2023 Safe Working on or near Low-Voltage and Extra-Low Voltage Electrical Installations and Equipment

AS/NZS 4836:2023 Safe Working on or near Low-Voltage and Extra-Low Voltage Electrical Installations and Equipment 4.3.15: 4.3.15 Leaving work unfinished

An unfinished work site must be left safe for others. Recommended measures: terminate exposed conductors to at least IP 2X (AS 60529) with mechanical protection or restraint; fit safety or information tags; use barriers or tape to keep unauthorised people out; tell relevant parties the work is incomplete and what hazards remain; make sure the installation cannot become energized; label switchboards and equipment clearly with their status; and give enough information for others to continue safely, including a handover procedure between shifts.