LV switchboards should be in dedicated switchrooms, risers or plantrooms with controlled access, or else have lockable devices against interference (HTM 06-02). Distribution boards should be in dedicated areas or lockable fire-resistant enclosures, with test certificates, LV schematics and current circuit charts beside or inside the door. In Medical Locations, RCDs and RCBOs are to be of type A or type B, rated 30 mA. A protection study by the designer or an independent specialist should confirm that all HV and LV devices discriminate to the agreed strategy, with time-delayed upstream RCDs where needed.