Because generators maintain supply when the network or PES has failed, their protection should be more tolerant: designers should obtain from makers the generator's damage characteristic and its short-circuit decrement behaviour before setting devices. Generators should supply enough fault current that a system earth fault is cleared while the set keeps running, whereas an earth fault on the cable linking the generator to the network should be cleared instantly; restricted earth fault plus overcurrent and network earth-fault relays may be used, graded with the decrement current in mind.