The alternate source must carry the total load for the designed duration and never under 2 hours. Generators need on-site fuel for at least 2 hours, fuel transfer pumps are fed from the standby system, sources may not depend only on public gas or municipal water (unless the AHJ approves a low risk of both failing together, which also lifts the on-site fuel rule), batteries and UPS for standby lighting last at least 90 minutes without load voltage dropping below 87.5 percent, automotive batteries are banned, automatic charging is provided, and dual fuel systems switch fuel automatically.