NFPA 110-2025 Standard for Emergency and Standby Power Systems 5.6.5.5-5.6.5.7: 5.6.5.5 to 5.6.5.7 Shutdown damper monitoring, panel approval and start initiation

Engines with an air shutdown damper need position contacts with local alarm and remote annunciation; the panel must be approved for the Level served; and cranking must be initiated by manual start, loss of normal power at any ATS in the EPSS, an exercise clock, a test switch in each ATS that simulates a power loss until reset, or, without an ATS, a loss of power signal.