AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 4: Additional requirements for generating sets connected by detachable connections – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 4.3: 4.3 Earthing and bonding of sets on detachable connections; no separate electrode

Earthing and bonding of plug-connected sets follow Section 2: the set's bonding system connects to the exposed conductive parts of supplied equipment and, where connected to an installation, to its earthing system through the lead. The protective earthing AS/NZS 3000 calls for is achieved by linking the portable set's bonding to the switchboard earth, so the Standard does not generally require its own electrode at the set (4.3.2.2). Winding neutral or centre points connect either to the set's bonding system or to the installation neutral as the Section 2 rules allow.