AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 4: Additional requirements for generating sets connected by detachable connections – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 4.2.6: 4.2.6 Marking of generator inlet fittings

Any inlet fitting for connecting a set must be permanently marked with its purpose, including wording that it is for isolated output generating sets only and that RCD-protected and centre-tapped sets must not be connected (A1 relocated this from 4.3.2.5).