AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 4: Additional requirements for generating sets connected by detachable connections – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 4.2.4: 4.2.4 Current limiting of each incoming generator supply

Each incoming supply from a set into the installation must be protected by its own overcurrent device inside the installation, operating in all active conductors with a setting not exceeding the lower of the supply cable rating and the inlet fitting rating; the generator's own overcurrent device does not satisfy this (A1 relocated this from 4.3.2.3).