AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.7.4: 2.7.4 Changeover device with intermediate off position used as a main switch

A permanently connected changeover device with a centre off position may take the place of the main switch, or of a switch for submains or final subcircuits, so the load can be fed from either source and isolated from both. A manual transfer switch used as a main switch must have a single-action mechanical manual operator (handle, lever, push buttons or similar); touch screens, programmable controls and the like must not be the means of operating it.