In Australia, switching the generator neutral at the changeover is not the recommended method for permanently connected sets; if done, the neutral switching must not disconnect the main switchboard MEN link connection. In New Zealand, no generator-neutral switching contact may be fitted for a permanently connected set feeding a board that holds a MEN link; where connection to such a board is impractical, the set may connect to a board without a MEN link using the IT-to-MEN conversion arrangement shown (neutral and earth bars labelled for generating set connections only, generator earth electrode, and a 100 mA RCD recommended for earth fault and earth potential rise protection).