Where sets are synchronised with a distributor's network the distributor's synchronising requirements must be obtained (most need a formal agreement for parallel operation). Automatic controls must keep output voltage and frequency synchronised with the normal supply during transfer or extended parallel running, or with other sets in a multiple-set installation, and synchronisation check controls must be fitted on every connection or changeover device used for paralleling, so it cannot close across unsynchronised sources.