AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.4.3: 2.4.3 Synchronization with the network or other sets

Where sets are synchronised with a distributor's network the distributor's synchronising requirements must be obtained (most need a formal agreement for parallel operation). Automatic controls must keep output voltage and frequency synchronised with the normal supply during transfer or extended parallel running, or with other sets in a multiple-set installation, and synchronisation check controls must be fitted on every connection or changeover device used for paralleling, so it cannot close across unsynchronised sources.