AS 1851:2012 Routine Service of Fire Protection Systems and Equipment 12.4.6-12.4.7: 12.4.6 and 12.4.7 Fire-rated glazing and fire-protected air ducts (yearly)

Fire-rated glazing, yearly: confirm none added, removed or modified against drawings; inspect for crazing or cracking at the perimeter and impact damage across the surface; verify the frame is not distorted, is anchored and free of defects or corrosion, has no visible through-gaps and is fire sealed at its junction with the surrounding construction; and check glazing seals are present and not deteriorated. Fire-protected air ducts, yearly: confirm none added, removed or modified; inspect the fire protection system or coating of fire-resistant ducts and supports against drawings and schedules and check for mechanical damage; look for deterioration or loss of adhesion of sprayed protection and for missing or loose boards and cladding; report any deficiency to the owner, representative or occupier and amend the schedule to keep it accurate. Damper operation is serviced under Section 13.