Every SEPSS is classified. Type is the longest gap in acceptable power the switched load may see (Table 4.2.2: Type O no break with the UPS carrying load, Type U a UPS with utility preferred, Type A a quarter cycle, Type B one cycle, Type 10 ten seconds, Type M manual). Class is the minimum time at rated load without recharge (Table 4.3: 2, 5, 15 or 90 minutes, or Class X as needed), and for batteries the table values assume end-of-life capacity.