IEC 61508:2010 - Functional Safety of E/E/PE Safety-related Systems
Part 2, Clause 7: E/E/PE lifecycle (hardware) – IEC 61508:2010 - Functional Safety of E/E/PE Safety-related Systems

IEC 61508:2010 - Functional Safety of E/E/PE Safety-related Systems 2-7.3.2: Part 2, 7.3.2 E/E/PE validation planning: requirements

Validation planning specifies the procedural and technical steps that will show the safety system meets the system safety requirements spec (SRS) and the design requirements specification. It considers every requirement in both specifications; the procedures and pass/fail criteria for showing each safety function is implemented correctly, and has the integrity required; the test environment including tools and equipment and which are to be calibrated; test evaluation procedures with justification; test procedures and performance criteria for validating the specified electromagnetic immunity limits; and policies for resolving validation failures.