The owner or operator must analyse and report one worst-case scenario for each Program 1 process and, for Program 2 and 3 processes, one for regulated toxics and one for regulated flammables giving the greatest distance to an endpoint, plus additional scenarios where another process's worst case would affect different public receptors. The worst-case quantity is the greatest amount in a single vessel or pipe, allowing for administrative controls. Toxic gases (including liquefied under pressure) are assumed released over 10 minutes; refrigerated liquefied gases likewise unless contained by passive mitigation in a pool deeper than 1 cm, in which case pool volatilisation at the boiling point applies. Toxic liquids are spilled instantaneously into a 1 cm deep pool (or the passively contained area), with volatilisation accounting for the highest three-year daily maximum temperature, the substance temperature and concentration. Flammable gases and liquids are assumed to form a vapour cloud explosion with a 10 percent yield factor for TNT-equivalent models (the whole gas quantity released over 10 minutes, or the quantity vaporised in the first 10 minutes from a pool). Distances use the 68.22 parameters with EPA's guidance or recognised public, commercial or proprietary models (proprietary models made accessible to the implementing agency and explained to local planners on request). Passive mitigation may be credited only if it would survive the event, and a smaller quantity at higher temperature or pressure, or closer to the boundary, must be chosen if it gives a greater offsite distance.