Arc blast and flash risk and resulting injuries must be taken into account when installations are designed, operated and maintained. Arc impedance can hold the arcing current below 50% of the prospective fault current, so protection may be slow to act and the arc lasts longer; injury comes mainly from radiant heat and the plasma fireball, and incident energy of about 1.2 cal/cm2 can cause second degree burns and ignite cotton clothing. Three-phase equipment protected at 63 A or more may exceed that level. Incident energy may be quantified with IEEE 1584 or an equivalent method, and a PCBU with high current equipment rated 800 A or more should commission an arc fault study within its hazard identification and control process; other installations may also need arc flash assessment. Arc faults can cause explosions, melt cubicles and throw debris, and protection devices may not operate to prevent them.