AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.7.9: 2.7.9 Automatic changeover back to normal supply and ATS used as a main switch

An automatic changeover device must return load to the normal supply only once its voltage and frequency have stayed normal on every phase for a set period (typically adjustable from 1 to 30 minutes, often 15), except that if the generator supply fails the transfer happens at once where normal supply is available; high-reliability sites may hold the transfer until a planned break suits operations, and a cool-down run may be needed before engine shutdown. An ATS used as a main switch must have a single-action mechanical manual operator, not a touch screen or programmable control.