AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.7.7-2.7.8: 2.7.7 Access and 2.7.8 identification of changeover devices

Only authorised people should be able to reach changeover devices, and any manual operating handle must sit at most 2 m above the standing surface. Devices must be permanently marked in English with their purpose and switch positions, terminals marked with the sources of supply, and a device that automatically brings an alternative supply into service must be permanently marked to say so.