AS/NZS 3010:2017 Electrical Installations Generating Sets 2.7.6: 2.7.6 Changeover device voltage, current and fault ratings

Changeover devices must be rated for at least the largest out-of-phase voltage that can appear across contacts tied to the two sources, and for the highest load current and fault duty available on either the normal or the generator supply.