A set acting as an alternative supply when normal supply fails needs at least one changeover device complying with the rest of Clause 2.7. Unless authorised otherwise, the changeover must prevent the set back-feeding the distributor's network. A grid-connected inverter or regenerative source must not be connected downstream of the changeover device (wording settled by A1), unless suitable controls prevent back-feed to the generator. Transfer switching equipment to AS/NZS 60947.6.1 or AS/NZS 3947.6.1 may satisfy this.