AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.6.2: 2.6.2 Overcurrent protection of outgoing circuits from the set

All outgoing circuits from a set must have overcurrent protection at the set unless AS/NZS 3000 allows another position or omission. Because available fault current depends on alternator type, regulator and engine power, devices must be chosen from overcurrent and alternator data. Exception: cables from a set to its switchboard need no short-circuit protection where installed to minimise short-circuit risk, for example inside one generator room of at least 2 hours fire rating as sheathed cables in a dedicated duct, on a dedicated or segregated tray, or as insulated busway up to the first protective device.

Maintained by Gerard Blokdyk

What else in your programme already covers this

This control maps to 1 controls across 1 other frameworks. If you already hold one of them, the evidence you collected for it is the starting point here rather than new work.

Every mapping shown was judged rather than inferred from wording similarity, and the ones that failed review are published too. See the coverage reports and what was rejected.

Other controls in Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

Query this from an agent

The graph holds this control, the 1 it maps to, and the evidence behind each claim, over MCP and REST.