Control conductors between the EPSS or SEPSS and transfer equipment or the controls that start emergency sources or connect emergency loads are kept independent of all other wiring, protected like feeders, and supervised for open, disconnected or shorted conductors; loss of integrity starts the generators or, for other sources, raises the malfunction signal of 700.6(A).