In assembly occupancies over 1000 persons, buildings with an occupied floor more than 75 ft above fire vehicle access, and educational occupancies over 300 occupants, emergency feeders must be in fully sprinklered areas or protected by a listed 2-hour circuit protective system, 2-hour fire-resistive cable, a 2-hour listed assembly holding only emergency circuits or concrete encasement, and feeder equipment such as transfer switches and panelboards must be in sprinklered spaces or 2-hour rated rooms (2026: same numbering).