AS/NZS 3000:2018 Electrical Installations (Wiring Rules)
Section 3: Selection and installation of wiring systems – AS/NZS 3000:2018 Electrical Installations (Wiring Rules)

AS/NZS 3000:2018 Electrical Installations (Wiring Rules) 3.9.4: 3.9.4 Protection of wiring against mechanical damage

Wiring fixed by fasteners, held by insulation or passing through structural members and concealed within 50 mm of the surface of a wall, ceiling, floor or roof is protected by mechanical protection of at least WSX3, earthed metallic armour or enclosure that operates short-circuit protection, or a 30 mA RCD; RCDs are otherwise not a substitute for mechanical protection, and wiring likely to be disturbed is supported and protected.