AS/NZS 3000:2018 Electrical Installations (Wiring Rules)
Section 3: Selection and installation of wiring systems – AS/NZS 3000:2018 Electrical Installations (Wiring Rules)

AS/NZS 3000:2018 Electrical Installations (Wiring Rules) 3.3: 3.3 External influences on wiring systems

Wiring is chosen for its environment: temperature, water and humidity, solid foreign bodies, corrosive substances, mechanical damage, vibration, flora, fauna, solar radiation and thermal insulation. Mechanical damage is minimised by the wiring's own characteristics, location or added protection. Cables passing through bulk thermal insulation are rated per AS/NZS 3008.1 by the length inside it: up to 150 mm as touching a surface, over 150 mm to 400 mm as partially surrounded, over 400 mm as completely surrounded.