Every emergency system overcurrent device must coordinate selectively with the protective devices both upstream and downstream of it, the selection made by a licensed professional engineer or another qualified person working mainly in electrical design, installation or maintenance, documented and made available to everyone responsible for designing, installing, inspecting, maintaining or operating the system. Replaced devices are reevaluated, and coordination is reevaluated after any modification, addition or deletion; two devices in series with no load in parallel on the downstream one are excepted.