1 to 3 points (1 to 2 Healthcare); applies to all eight BD+C adaptations. Provide glare-control devices in regularly occupied spaces and then simulate spatial daylight autonomy (average sDA300/50% of 40%, 55% or 75%, with ASE1000,250 over 10% addressed), or simulate illuminance of 300 to 3,000 lux at 09:00 and 15:00 on an equinox day for 55%, 75% or 90% of floor area, or measure illuminance in the occupied building.