A documented overall safety validation plan states when validation happens and who performs it; the relevant EUC operating modes (set-up and adjustment, start-up, teach mode, manual, semi-automatic and automatic running, steady state, reset, shutdown, maintenance and foreseeable abnormal conditions) and which safety systems must be validated in each before commissioning; the technical strategy (analysis, statistical testing and similar); the measures and procedures confirming that allocation was done correctly and that each safety function meets both the functions and the integrity requirements; explicit reference to each element in the outputs of 7.5 and 7.6; the validation environment including calibrated equipment; pass and fail criteria; and how results, particularly failures, are evaluated.