Validation follows the 7.8 plan. Equipment used for quantitative measurement is calibrated with traceability back to a national standard, or else the vendor's own specification. The records hold the version of the overall safety requirements spec used; the validation activities in chronological order; the safety function validated and whether by test or analysis; tools and equipment with calibration data; results; configuration identification of the item, procedures and environment; and discrepancies between expected and actual results. For each discrepancy the analysis and the decision to continue or raise a change request and step back to an earlier step are recorded.