AS/NZS 3000:2018 Electrical Installations (Wiring Rules)
Section 6: Damp situations – AS/NZS 3000:2018 Electrical Installations (Wiring Rules)

AS/NZS 3000:2018 Electrical Installations (Wiring Rules) 6.2: 6.2 Baths, showers and other fixed water containers

Zones around baths and showers are classified (for fixed shower connections, Zone 1 extends 1.2 m radius; in Australia a 0.6 m dimension may be reduced by a 1.8 m barrier; other water containers up to 40 L have Zones 0 and 2); minimum ratings are IPX7 for Zone 0 and IPX4 for Zones 1 and 2; prohibited measures and equipment rules apply, and generation systems and batteries may not be installed in any classified zone.