AS/NZS 3000:2018 Electrical Installations (Wiring Rules)
Part 1: Scope, application and fundamental principles (Section 1) – AS/NZS 3000:2018 Electrical Installations (Wiring Rules)

AS/NZS 3000:2018 Electrical Installations (Wiring Rules) 1.5.7: 1.5.7 Basic and fault protection by extra-low voltage

SELV or PELV may provide both basic and fault protection where the source is limited to 50 V (a.c.; 120 V for ripple-free d.c.), circuits are segregated from each other and from higher voltages, SELV live parts are not earthed or connected to other circuits' earths, and PELV live parts are insulated or behind barriers unless below set lower voltages (Clause 7.5 has the detailed rules).