Hose is serviced yearly, after use and whenever defects are suspected. The routine: lay the hose out, preferably straight on a flat clean surface, and check the jacket for cuts, abrasion, burns or contamination; inspect couplings for damaged or distorted threads, lugs or gaskets; check storage (folds not in the same place each time, on bollards or flaked, or, where staff are trained for it, coiled on a bight with both couplings reachable, tag visible); hydrostatically test the hose by marking the coupling joints, restraining the ends, charging to a nominal 500 kPa while venting air, raising the pressure over 20 s to 2 min to the class maximum working pressure (Class L 1000 kPa, Class M 1400 kPa, Class H 2100 kPa) and holding it at least 3 minutes while checking for defects, leaks and coupling movement; clean dirty hose; and dry wet hose (other than extruded types) before storage, with heated drying kept to 40 degrees C, with airflow and for no more than 12 hours.