AS 1684.2:2021 Residential Timber-Framed Construction - Non-Cyclonic Areas
Section 3: Substructure – AS 1684.2:2021 Residential Timber-Framed Construction - Non-Cyclonic Areas

AS 1684.2:2021 Residential Timber-Framed Construction - Non-Cyclonic Areas 3.6: 3.6 Subfloor supports: loads and footing size

Stumps, posts, piers and similar under the floor are designed for vertical gravity loads using the procedure: determine dead and live loads (floor systems by weight, walls at 0.4 kPa over the floor area, sheet roofs 0.4 kPa and tiled 0.9 kPa, floor live load 1.5 kPa, decks over 1.0 m at 3.0 kPa unless over 40 square metres, plus snow above 0.2 kPa in alpine areas), combine them, and size the footing from the table or the allowable bearing pressure. It applies to site classes A, S, M and H with at least 100 kPa bearing, classified to AS 2870; E and P sites need professional advice.

Maintained by Gerard Blokdyk

Other controls in Section 3: Substructure – AS 1684.2:2021 Residential Timber-Framed Construction - Non-Cyclonic Areas

Query this from an agent

The graph holds this control, the 0 it maps to, and the evidence behind each claim, over MCP and REST.