In the predecessor, switches and controls on the accessible path (other than power outlets) are 900 mm to 1100 mm above floor and at least 500 mm from internal corners unless on the latch-side architrave; in accessible sole-occupancy units and sanitary facilities, rocker or toggle switches are at least 30 mm by 30 mm (push pads also have a minimum size), and power outlets are 600 mm to 1100 mm above floor and at least 500 mm from internal corners.