1 point; applies to all eight BD+C adaptations. For all exterior luminaires, meet uplight limits and light trespass limits by lighting zone of the IES/IDA Model Lighting Ordinance, using the BUG rating method (uplight U0 to U4, backlight and glare ratings by mounting distance from the lighting boundary) or the calculation method (0 to 6% of lumens above horizontal; vertical illuminance at the boundary of 0.05 to 0.60 footcandles); keep internally illuminated signage to 200 nits at night and 2,000 by day. Listed exemptions (transport signals, theatrical, roadway, emergency departments, flags, late-night facade lighting in zones 3 and 4) must be separately controlled.