IEC 62351 - Power Systems Communication Security
Part 5: security for IEC 60870-5 and derivatives – IEC 62351 - Power Systems Communication Security

IEC 62351 - Power Systems Communication Security 5:5.3: Part 5, 5.3: design issues of the telecontrol environment

The mechanism is designed for asymmetric controlling and controlled stations (different message formats each way, session keys issued by the controlling station), message-oriented protocols needing per-message authentication, protocols without usable sequence numbers (so the mechanism carries its own), limited processing power (avoiding heavy public-key operations where possible), limited bandwidth down to 1,200 bit/s with per-octet charging (so authentication data is short), no access to an online authentication server, frame lengths of 255 octets or less, limited checksums, radio and dial-up media, many affected protocols with differing data link layers, remote sites and unreliable media.

Maintained by Gerard BlokdykControl text last updated

Other controls in Part 5: security for IEC 60870-5 and derivatives – IEC 62351 - Power Systems Communication Security

Query this from an agent

The graph holds this control, the 0 it maps to, and the evidence behind each claim, over MCP and REST.