Conformance testing of IEC 62351-6 implementations uses a test environment that resembles the final one as closely as it can with a test equipment able to publish or subscribe and a certificate authority, runs non-intrusively with the device under test carrying its production software, covers normal procedures and resiliency (fault) behaviour at least once, executes within the context of an application, requires prior base-protocol conformance with the same firmware and the PICS and PIXIT documents, accredited test laboratories, and separate test cases for subscriber-type and publisher-type devices.
The graph holds this control, the 0 it maps to, and the evidence behind each claim, over MCP and REST.