Article 13 requires Member States to set system requirements in relation to the overall energy performance, the proper installation, and the appropriate dimensioning, adjustment and control of the technical building systems (TBS) installed in existing buildings, namely heating, hot water, cooling, ventilation, large built-in lighting, building automation and control (BACS), on-site renewable energy systems, on-site electricity generation, EV recharging infrastructure, and combinations of the above. Article 13(8) requires non-residential buildings with effective HVAC output over 290 kW to be equipped with BACS by 31 December 2024; over 70 kW by 31 December 2029. Article 13(13) requires residential building automation similarly.