AS/NZS 4836:2023 Safe Working on or near Low-Voltage and Extra-Low Voltage Electrical Installations and Equipment
Section 5: Elevated equipment, poles, structures and overhead conductors – AS/NZS 4836:2023 Safe Working on or near Low-Voltage and Extra-Low Voltage Electrical Installations and Equipment

AS/NZS 4836:2023 Safe Working on or near Low-Voltage and Extra-Low Voltage Electrical Installations and Equipment 5.3-5.4: 5.3 and 5.4 Conductive poles and structures, and erecting equipment near live conductors

Extra care is needed near earth situations, earth wires, conductive fittings and concrete or metal poles. When working on isolated LV lines carried on conductive poles or structures (and wooden poles carrying exposed earth downleads or bonding leads, LV neutrals excepted), the lines must be temporarily connected electrically to each pole or structure, unless the line is treated as live under live work procedures, work is from an insulated EWP placed to prevent simultaneous contact with pole and conductor, or exposed conductive parts are effectively covered with insulation. Precautions must stop equipment or conducting materials, building materials included, from encroaching on minimum safe approach distances to exposed live conductors while being erected; if that cannot be achieved, the conductors must be de-energized.